Notice!
If Lockout Report is enabled for any zone, the last restore signal is not transmitted until the
system is disarmed.
Example
Zones 1 and 2 are programmed for lockout report with a Swinger Shutdown Count of 6. If
Zone 1 activates an alarm, the Swinger Shutdown Count increments to 1 when the control
panel sends the reort.
If Zone 1 reactivates the report, the Swinger Shutdown Count is incremented to 2. If Zone 1
reactivates the report three more times, the Swinger Shutdown Count is 5.
If Zone 2 activates an alarm, the Swinger Shutdown Count for Zone 2 is incremented to 1.
Swinger Shutdown Count for Zone 1 is still 5. If Zone 1 reactivates again, it locks out Zone 1
from activating the report until the system is reset. At this point, the Swinger Shutdown Count
for the Report is reset to 0 and Zone 1 is locked out. When smart lockout is enabled, if any
zone activates the siren before siren running time is expired, Zone 1 reactivates and can still
send a report.
System Status Programming
System Status Reporting Options
Location 427 is set by default to report only to Receiver 1. You can select whether System
Status Reports are sent to Receiver 1, Receiver 2, or both, Receiver 2 only when Receiver 1
fails, or no reporting.
Item Location Default
System Status Reporting Options 427 1
Value Description
0 No Reports allowed
1 Report to Receiver 1
2 Report to Receiver 2
4 Report to both Receiver 1 and Receiver 2
8 Report to Receiver 2 only if Receiver 1 fails
Test Reporting Time
A Test Report (Contact ID Event Code 601/602) is a specific signal sent to the base station
receiver and is normally used to test the dialing and reporting functions of the control panel.
When programming Test Report options, specify the hour and minute of the day the report is
required, and how often to send the report. Test reports are reported on a daily basis from
every day to every fifteen days. Program the Test Report Time as 34:00 to send reports every
60 minutes.
Example
Set auto test report interval to the 37
th
minute of every hour, the time needs to be set as
34:37. Then the auto test report will be sent at 00:37, 01:37, 02:37, etc.
If you want to send Test Reports once every seven days at 11:35 PM (23:35), program
Locations 428 to 431 as [2 3 3 5] and location 434 as [7].
9.6
9.6.1
9.6.2
98 en | Zone Information Control Panel
2014.07 | 00n | F01U298026 Installation Guide