Zone Information
Day Alarm Information
Location 265
Default 0
1 Zone 1
2 Zone 2
4 Zone 3
8 Zone 4
This location has four programming options. You can select any combination of the options by
programming a single value. Calculate this value by adding the option bit numbers together.
Day Alarm allows some zones to be monitored when the system is disarmed. Indications are
available at any of the programmable outputs, including the codepad buzzer. This function
accommodates latching and non-latching Day Alarm Output Event Types.
When the system is armed in AWAY Mode, STAY Mode 1, or STAY Mode 2, zones programmed
as Day Alarm Zones activate the sirens and report just as non-Day Alarm Zones do. When Day
Alarm is activated, it ignores any zone Pulse Count settings programmed for that zone (that is,
the zone Pulse Count is only relevant when the system is armed).
Example
You can set up a Day Alarm at the front door of a shop with a pressure mat or electronic beam
that is activated when a customer enters the shop. When a customer walks on the pressure
mat or breaks the electronic beam, the codepad buzzer beeps.
Day Alarm Resetting
An output that is programmed for Day Alarm Resetting operates when a zone programmed for
Day Alarm is activated. The output is reset after the zone is resealed. This occurs only when
the system is disarmed. Refer to Output Event Types, page 132 for more information.
Day Alarm Latching
An output that is programmed for Day Alarm Latching operates when a zone programmed for
Day Alarm is activated. The zone indicator and the latching output resets when [AWAY] is
pressed. This occurs only when the system is disarmed. Refer to Output Event Types, page 132
for more information.
Day Alarm Operation
If a zone is programmed for Day Alarm, the zone can be isolated in the normal way so that it
does not register as a Day Alarm Zone when the system is disarmed. You can use only Zones 1
to 4 as Day Alarm Zones.
You can program the STAY indicator to indicate whether Day Alarm is turned on or off by
selecting Option 8 in Location 496 (refer to Consumer Options 1, page 108). When Day Alarm
is on, the STAY indicator flashes once every 3 seconds.
You can program an output to mimic a zone for monitoring Zones 5 to 8. Refer to Output Event
Types, page 132.
To turn Day Alarm on:
Press and hold [4] until three beeps sound.
9
9.1
9.1.1
9.1.2
9.1.3
Control Panel Zone Information | en 83
Installation Guide 2014.07 | 00n | F01U298026