3. Enter [9 5 9 #]. Two beeps sound after a successful test of the direct link adapter. A long
beep indicates that the direct link adapter data is corrupt and must be erased to clear the
corrupt data.
4. Enter [9 6 0 #] to exit from Installer’s Programming Mode. The STAY and AWAY indicators
are extinguished on the codepad and the system returns to the disarmed remote state.
5. Remove the direct link adapter from the control panel. Failure to exit from Installer’s
Programming Mode before removing the direct link adapter can corrupt the data in the
direct link adapter.
Command 960 - Save and exit from Installer's Programming Mode
This command saves and exits from Installer’s Programming Mode. You can exit from
Installer’s Programming Mode from any location.
To exit from Installer’s Programming Mode:
Enter [9 6 0 #]. The system returns to the disarmed state. When using the remote codepad,
the STAY and AWAY indicators are extinguished.
Command 961 - Reset the Control Panel to Factory Default Settings
This command resets the control panel to factory default values. You can reset the control
panel from any location.
To reset the control panel to factory defaults:
1. Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
remote codepad to indicate that you entered Installer’s Programming Mode. The remote
codepad displays the data stored in Location 0000.
2. Enter [9 6 1 #]. Two beeps sound and the system is reset to the factory default values.
Command 962 - Copy the Control Panel Memory to the IUI-SOL-ADAPTER
This command copies the control panel memory to the direct link adapter. You can only use
the IUI-SOL-ADAPTER Direct Link Adapter with the control panel.
To copy the control panel memory to the direct link adapter:
1. Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
remote codepad to indicate you entered Installer’s Programming Mode. The remote
codepad displays the data stored in Location 0000.
2. Connect the direct link adapter to the Bosch SDI2 Bus pins at the bottom of the control
panel printed circuit board.
3. Enter [9 6 2 #].Two beeps sound after the control panel memory is successfully copied to
the direct link adapter. A long beep indicates that the direct link adapter is corrupt and
must be erased to clear the corrupt data.
4. Enter command [9 6 0 #] to exit from Installer’s Programming Mode. The STAY and AWAY
indicators are extinguished on the remote codepad to indicate the system is disarmed.
5. Remove the direct link adapter from the control panel. Failure to exit from Installer’s
Programming Mode before removing the direct link adapter can corrupt the direct link
adapter.
Command 963 - Copy the IUI-SOL-ADAPTER to the Control Panel
This command copies data from the direct link adapter to the control panel. You can only use
the IUI-SOL-ADAPTER Direct Link Adapter only with the control panel.
5.1.3
5.1.4
5.1.5
5.1.6
Control Panel Configuration | en 43
Installation Guide 2014.07 | 00n | F01U298026