DS7400XiV4-EXP | Reference Guide | 3.0 Control Panel Installation EN | 17
Bosch Security Systems | 1/05| 4998154963B
Figure 7: Zones 1 to 8 Wiring
17 18 19 20 21 22 23 24 25 26 27 28 29 30
PO1 PO2
1–
L+
2– 3– 5– 6– 7– 8–4–
L+ L+ L+
EOL = 2.2k
3.8 Programmable Output Wiring
See Figure 7, Terminals 17 and 18. PO1 shorts to aux.
power negative when activated. PO1 can sink up to 1.0
A. PO1 function is programmed in Address 2735. See
Section 5.9.6 Output Programming.
PO2 supplies 12 V and up to 500 mA when activated.
PO2 function is programmed in Address 2736. See
Section 5.9.6 Output Programming.
Figure 8: Typical Burglar and Fire Wiring
NO
Z– L+ Z– L+
++
–
–
++
–
Z– L+
NC
1
9
8
7
6
5
432
1011
1 12
5
6
7
1- Zone Input
2- Loop +
3- Loop + or PO2
4- Aux. Power – Terminal 5 or 7(see Figure 3)
5- Power in
6- Power out
7- Alarm
8- End-of-line supervision relay (for example,
EOL200)
9- Typical 4-wire smoke detector wiring (for
example, DS250 in an MB4W base)
10- Typical 2-wire smoke detector wiring
(EOL = 2.2k)
11- Typical burglar alarm loop wiring (EOL = 2.2k)
3.9 Option Bus Wiring
See Figure 9. Used for options such as the DS7416i
Communications Module, the DS7420i Dual Phone
Line Module, and so on. Also for Keypads 11 to 15.
For Commercial Fire Mode, Option Bus wiring should
be in conduit if run outside the enclosure.
Figure 9: Option Bus Wiring
R
B
G
Y
1
1- Option Bus
3.10 Hardware Layout Example
See Figure 10.
• Up to 15 keypads can be used. Keypads 1 to 10
connect to the Keypad Bus and Keypads 11 to 15
connect to the Option Bus. One keypad must be
designated as Keypad 1 and connected to the
Keypad Bus. See the DS7447E/DS7447V2,
DS7445i/DS7445V2, and DS7448 Installation
Instructions for further details.
• A DS7420i (Dual Phone Line/Bell Supervision
Module) can be connected to the control panel,
and placed within the enclosure. Connect to the
Options Bus of the control panel. See the
appropriate keypad Installation Instructions for
further details.
• Up to two DX3010 Octal Relay Modules can be
connected to the control panel and placed within
the enclosure. Connect to the Option Bus of the
control panel. This provides an additional 8 Form
“C” relay outputs for the Control Panel. See the
DX3010 Installation Instructions for further details.
• A DS7430 or a DS7436 (Multiplex Expansion
Module) can be connected to the control panel
using the expansion port. This allows for the
connection of additional zones using the Option
Bus. See the DS7430 or DS7436 Installation
Instructions for further details.
• Up to 30 DS7432E 8-Input Remote Modules can
be connected to the DS7430 or DS7436. Connect
to the Power and Bus Terminals of the Multiplex
Expansion Module. This allows for a means of
addressing up to 240 input loops of conventional
contacts to the control panel. See the DS7432E
Installation Instructions for further details.