DS7400XiV4-EXP | Reference Guide | 6. Troubleshooting Guide EN | 104
Bosch Security Systems | 1/05| 4998154963B
Table 137: Zone Troubleshooting (continued)
Symptom Probable Cause Possible Solutions
Invisible or silent zone activates alarm
output.
The output is programmed as "latch on
alarm" (0).
Program the output to follow zone
alarms (6).
Keypad displays Fire Trouble, but does
not indicate any zones.
A ground fault condition exists. See #87 display = Ground Fault on
page 106.
Keypad displays Not Ready, but no
zone number is displayed.
An invisible zone is not ready. Press [PIN][OFF] to display the zone
number of the invisible zone that is not
ready.
6.4 General System Problems
Table 138: General System Troubleshooting
Symptom Probable Cause Possible Solutions
Cannot set the programming values to
the factory default.
Enter a value of 01 in address
4058.
Only enter a value of 01 in
address 4058 when you are sure you
want to default the programming.
Doing so immediately erases all
programming.
Power LED is flashing, keypad displays
Control Trouble Press #87.
A control panel trouble exists. Press [#][8][7] to determine the trouble
condition.
#87 display = Oct. Relay Fault
#89 display = System Fault 20
a. The octal relay module
(DX3010) is defective or the
wiring to the module is
defective.
b. There is no DX3010 or a
DX3010 was removed from
the system.
a. Check the wiring to the module.
b. Enter, then exit programming mode.
This rescans the option bus and clears
the problem.
#87 display = Multiplex Bus Fault
The Multiplex Bus is defective or
shorted.
Check wiring for shorts.
Cannot reset to factory default. Keypad programming access is set
to PARTIAL from remote
programmer.
Change setting to FULL from the Remote
programmer.
#87 display = RAM Fault
#89 display = System Fault 01
OR
#87 display = ROM Fault
#89 display = System Fault 02
OR
#87 display = EEProm Fault
#89 display = System Fault 03
a. An EEPROM fault can be caused by
disconnecting power from the control
panel when it is in Programmer’s
Mode. In this case, enter then exit
program mode to clear.
b. Try to clear the error at the keypad by
entering a PIN then Reset.
c. Remove AC and battery power, then
re-apply. Event history is lost and
time/date must be reset.
d. If error persists, return the control
panel to factory default programming
by setting program address 4058 to
"01". If the error clears, re-program the
control panel.
e. If error still persists, replace the control
panel.