DS7400XiV4-EXP | Reference Guide | 7. Reference Materials EN | 118
Bosch Security Systems | 1/05| 4998154963B
Close: This report is sent when the system has been
armed. In SIA or Contact ID formats, the user number
for the person who armed the system will be sent with
this report. To send the user number along with a Close
report in other formats, program the extended digit of
the report as *5. In Contact ID format, the area number
will also be sent along with this report.
Duress: This report is sent when the system is disarmed
using a duress code. The user number is not sent with
this report.
Partial Close: This report is sent when the system is
armed partially, or force armed.
First Open After Alarm: This report is sent when the
system is disarmed after an alarm has occurred.
Low Battery: This report is sent when a low battery
condition occurs.
Battery Restoral: This report is sent when a low
battery condition restores.
AC Fail: This report is sent when an AC failure
condition occurs. This report may be delayed in address
4034.
AC Failure Report Delay: The AC power loss report
can be programmed to delay for up to 254 minutes (see
Section 5.9.21 AC Fail Report Delay Programming). (The
same delay would also apply to the AC restoral report.)
If another report is sent during this delay period,
the AC fail report will be sent along with this
report.
If the AC power restores during this delay period,
the AC loss report will not be sent.
Programming address 4034 as FF causes the report
to be sent at a random interval of at least 15
minutes, but no more than 2 hours after the AC
failure occurs.
AC Restoral: This report is sent when an AC failure
condition restores.
Communicator Test/System Normal: This report is
sent at the 24-hour check-in time if there is not a control
panel trouble, an active fire alarm that has not been
acknowledged, a fire trouble, or a supervisory
condition. Note: To send a Communicator Test even if
one of these conditions exists, program the
Communicator Test/System Off Normal.
Remote Program Successful: This report is sent after a
Remote Program session, if the session was terminated
properly.
Remote Program Unsuccessful: This report is sent
after a Remote Program session, if some error has
occurred or the session did not terminate properly.
Local Program Successful: This report is sent when
local programmer's mode is exited and there is no
error associated with the programming.
Local Program Unsuccessful: This report is sent
when local programmer's mode is exited and there has
been some error associated with the programming.
System Trouble: This report is sent when a control
panel trouble condition occurs.
System Trouble Restoral: This report is sent when all
system trouble conditions restore.
Communicator Test/System Off Normal: This
report is sent at the 24-hour check-in time if there is a
control panel trouble, an active fire alarm that has not
been acknowledged, a fire trouble, or a supervisory
condition.
Exit Error: This report is sent if an exit error occurs.
An exit error occurs when an entry/exit zone is still
violated at the end of the exit delay. If this happens,
the entry delay will begin and any output programmed
to activate an alarm will energize. If the system is not
disarmed before the entry delay expires, an alarm
report for the effected zone will be sent and the Exit
Error report will be sent. If this report is not
programmed, the control panel will not sound the exit
error warning.
Recent Closing: This report is sent, along with any
alarm reports, when there is an alarm within the first
five minutes after the system has been armed.
System Walk Test: This report is sent when a system
test has been started ([#][8][1] key sequence). Zone
reports are sent during a system test.
System Walk Test Restoral: This report is sent when
the system test has been completed or has timed-out.
Fire Walk Test: This report is sent when a Fire Walk
Test has been started ([#][9][1] key sequence). Zone
reports are not sent during a Fire Walk Test.
Fire Walk Test Restoral: This report is sent when the
Fire Walk Test has been completed or has timed-out.
Dirty Chamber Report: This report is sent when a
MX250 Series smoke detector fails to pass the
"Chamber Check
®
" sensitivity test.
Dirty Chamber Restoral: This report is sent when a
MX250 Series smoke detector has been returned to
normal operation after service.