DS7400XiV4-EXP | Reference Guide | 3.0 Control Panel Installation EN | 13
Bosch Security Systems | 1/05| 4998154963B
Table 6: Options (continued)
Module Description Current Draw
MX775i Multiplex Passive
Infrared (PIR)
Intrusion Detector
200 µA, Standby; 2 mA
in Walk Test mode
MX794i The MX794 is a
Long Range
Multiplex PIR
Intrusion Detector
with Self-test.
800 µA, Standby; 2
mA, Alarm.
MX934i Multiplex Passive
Infrared (PIR)
intrusion detector.
200 µA, Standby; 2 mA
in Walk Test mode.
MX938i 360° Ceiling
Mount Multiplex
PIR Intrusion
Detector.
200 µA, Standby; 2.5
mA in Walk Test mode
DACM Door Access
Control Module
RF3222
RF3222E
120-zone Wireless
Receiver (up to
two receivers per
system. Requires
use of a DS7430
or DS7436
Multiplex
Expansion
Module.)
30 mA
2.5 Control Panel Package Formats
The control panel is also available in three package
formats:
Table 7: Package Formats
Package Description
DS7400XiF DS7400Xi in large red enclosure
manufactured from 1.2 mm (18 gauge)
cold-rolled steel, measuring 38.1 cm x
52.7 cm x 10.8 cm (15.0 in. x 20.75 in.
x 4.25 in.) (H x W x D).
DS7400XiFCP DS7400XiF package with DS7420i,
DS7447E/DS7447V2 and a AE-TR16.
DS7400XiCC DS7400Xi in an Attack Enclosure.
3.0 Control Panel Installation
The DS7400XiV4 Control Panel and the enclosure are
shipped together. The control panel, however, must be
installed into the enclosure. Hardware for mounting
the enclosure to a wall, and the control panel to the
enclosure is located in its own hardware pack.
Before servicing, remove all power
including the transformer, battery, and
phone line. A complete functional test is
required after any programming.
Incorrect connections may result in damage
to the unit.
The system is power limited except for
battery terminals. All wiring entering this
enclosure must be power limited.
An appropriate two-pole disconnect device
must be installed by qualified service
personnel, as part of the building installation.
3.1 Install the Enclosure
1. Knock out the desired wire entrances on the
enclosure.
2. Use the enclosure as a template and mark the top
mounting holes on the mounting surface.
3. Pre-start the screws (not supplied) for these holes.
4. Place the enclosure onto these screws. See Figure 1.
5. Tighten the screws.
6. Screw in the remaining two screws into the bottom
holes. See Figure 1.
Use proper anchor and screw sets when
installing the enclosure on non-load-
bearing surfaces, such as dry wall.
Use the screws provided to secure the
enclosure cover (see Figure 1).