10-80 Handling, Diagnostic and Service Functions MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Error Messages in the Case of Serial Communication
The error codes defined in the SERCOS interface specification are used
for the different errors (see "Specification SERCOS interface", section
7.4.2.3 "Service channel error messages"). These codes are also used in
the case of incorrect access to control and system parameters.
Error code Description
0x1001 no IDN
0x1009 invalid access to element 1
0x2001 no name
0x2002 name transmission too short
0x2003 name transmission too long
0x2004 name cannot be changed (read only)
0x2005 name is write-protected at this time
0x3002 attribute transmission too short
0x3003 attribute transmission too long
0x3004 attribute cannot be changed (read only)
0x3005 attribute is write-protected at this time
0x4001 no units
0x4002 unit transmission too short
0x4003 unit transmission too long
0x4004 unit cannot be changed (read only)
0x4005 unit is write-protected at this time
0x5001 no minimum input value
0x5002 minimum input value transmission too short
0x5003 minimum input value transmission too long
0x5004 minimum input value cannot be changed (read only)
0x5005 minimum input value is write-protected at this time
0x6001 no maximum input value
0x6002 maximum input value transmission too short
0x6003 maximum input value transmission too long
0x6004 maximum input value cannot be changed (read only)
0x6005 maximum input value is write-protected at this time
0x7002 operation data transmission too short
0x7003 operation data transmission too long
0x7004 operation data cannot be changed (read only)
0x7005 operation data is write-protected at this time (e.g. communication
phase)
0x7006 operation data is smaller than the minimum input value
0x7007 operation data is greater than the maximum input value
0x7008 invalid operation data
0x7009 operation data write protected by a password
0x700A operation data is write protected, it is configured cyclically
0x700B invalid indirect addressing (e.g., data container, list handling)
0x700C operation data is write protected, due to other settings
(e.g., parameter, operation mode, drive enable, drive on etc.)
Fig. 10-40: Error specification according to SERCOS