MPH-02, MPB-02, MPD-02 Master Communication 4-57
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
The enable signal is accepted, i.e. the drive switches from its de-
energized status to its energized status, when the following conditions
have been fulfilled:
There mustnt be any drive error present.
The drive must be in operating mode (phase 4).
Power must have been switched on and the DC bus voltage must be
above the defined minimum threshold (see also "Voltage Monitor in
DC Bus" in chapter "Drive Functions").
The drive displays this status on the control panel with "Ab". The
diagnostic drive message in parameter S-0-0095, Diagnostic
message is A0012 Control and power sections ready for
operation.
The signal "ready" in parameter P-0-0115, Device control: Status
word must have been set (P-0-0115, bit 1 = 1).
When drive enable is set and the "Drive Halt" signal is active (P-0-4028,
bit 13 = 0),
the display of the control panel changes to "AH" and
the diagnostic drive message then is A0010 Drive HALT and thereby
signals the activation of "Drive Halt".
If the "Drive Halt" signal is then deactivated (P-0-4028, bit 13 = 1),
the display of the control panel changes to "AF" and
the diagnostic drive message then is A0206, A0207, A0210 or A0211
(positioning block mode) and thereby signals the activation of the
operating mode.
Note: The "Drive Halt" signal is status-controlled and active when the
signal = 0 V.
A positive edge at the "clear error" input starts the command for error
clearing. By default setting the command for error clearing C0500 Reset
class 1 diagnostics, error reset has been assigned to a digital input on
the parallel interface.
Note: By activating the command for error clearing all drive errors
are cleared!
Configurable Digital Inputs
The signal control word for IndraDrive devices is cyclically generated or
cyclically transmitted to the I/O module:
cycle time "Advanced" T = 250 µs
cycle time "Basic" T = 500 µs
Note: The digital inputs of the parallel interface are mapped to those
of parameter S-0-0145, Signal control word.
"Drive Halt" Signal
Clearing Errors
Cycle Time