D7212GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 86
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
P## Entry Delay
Default: Refer to the program record sheet
Selection: 5 sec to 600 sec
Use this option to enter the amount of entry delay time
that a user has after faulting a Controlled point (
P##
Type 1, 2, 3
) with a delayed response (D) (
P## Pt
Response
) of 4, 5, 6, 7, or 8. DISARM NOW appears for
the duration of the time programmed when the point
is faulted in the delay condition.
The D1255 alternates between DISARM
NOW and the point text of the point that
caused the area to enter into entry delay.
If this time expires before disarming, or if the point is
faulted to an instant response (I), an alarm occurs.
Make entries in 5-sec increments. The
programmer does not allow off-increment
entries.
When the control panel is in Entry Delay, entering a
valid Passcode disarms the system as soon as the last
digit of the Passcode is entered. No other keys are
required. When the control panel is in Exit Delay or is
armed, entering a valid Passcode must be followed by
the [ENTER] or [ENT] key.
If another Perimeter or Interior Follower
Delay point activates while the area is
already in entry delay, the control panel
adjusts the delay time to the Delay point
with the least amount of delay time.
When a user enters an area, a Perimeter
point is faulted and the entry delay starts. If
an interior point must fault during entry
delay to allow the user to disarm the area at
a keypad, program P## Type as 3 (Interior
Follower).
For SIA CP-01 Compliance:
P## Entry Delay
must be between 30 sec and
240 sec.
P## Ent Tone Off
Default: No
Selection: Yes or No
Yes
Disables the entry delay tone when
this perimeter point is faulted.
This is intended for use with points
set to
P## Type 1
(Perimeter).
No
A tone sounds at keypads when this
point starts entry delay.
This option enables and disables the entry delay
warning tone for this point.
Do not set points to No if they are actually
used to notify the user to disarm the system.
The possibility of false alarms increases if
the entry delay warning is not used.
Entry Tone can also be turned off when
programming your CC Entry Tone, in
Section 2.10 Keypad (Command Center)
on page 46, that allows you to manage the
tone by keypad.
You might want to disable the entry tone in
high security applications where you do not
want to annunciate entry delay.
P## Silent Bell
Default: No
Selection: Yes or No
Yes
Activate the Silent Alarm relay when
this point enters into alarm. Keypads
do not sound the alarm tone for Non-
fire points.
No
Activate either the Fire Bell relay or
Alarm Bell relay and sound the alarm
tone at keypads when this point
enters into alarm. If this is a Fire
point, it activates the Fire Bell relay
programmed in Relay Parameters.
Otherwise, it activates the Alarm Bell
relay. The amount of time and
pattern of the relay activation is
programmed by area in Bell
Parameters.