6.7 Route Group Attempts
This section determines how many times a route group
tries the primary destination before trying the backup
destination if the primary destination fails. This entry
applies to both Phone numbers and IP addresses.
RG# 1 Attempt
Default: No
Selection: Yes or No
Yes
This route group tries the primary
destination once and, if unsuccessful,
tries the backup destination. The
control panel still makes a total of ten
attempts (five to the primary, five to
the backup) before generating a route
group Comm Fail Event.
No
This route group tries the primary
destination twice and, if unsuccessful,
tries the backup destination. The
control panel makes a total of ten
attempts (six to the primary, four to
the backup) before generating a route
group Comm Fail Event.
6.8 Miscellaneous
Fire Summary Sustain
Default: No
Selection: Yes or No
Yes
Forces the
Summary Fire
relay
output to remain on after the Alarm
Silence command.
No
Allows
Summary Fire
relay output
to be silent when the Fire Alarm Bell
output is silenced and all Fire Points
return to normal.
Use this parameter to set the Summary Fire relay
output to continue or to stop after the Fire Alarm Bell
is silenced or times out. Refer to the
Summary Fire
prompt in Section 2.13.2 Panel-Wide Relays on page 74.
Fire Supv Res Type
Default: 0
Selection: 0, 1, 2
0
The control panel sends a FIRE
TROUBLE RESTORE when a Fire
Supervision point restores to normal.
1
The control panel sends a FIRE
ALARM RESTORE when a Fire
Supervision point restores to normal.
2
The control panel sends a FIRE
SUPERVISION RESTORE when a
Fire Supervision point restores to
normal.
Determines how the control panel sends a Fire
Supervision Restoral Event.
The Fire Supv Restore Event is part of Fire
Events in Routing. If Fire Supervision
Restore Events are needed, simply enable
them in Routing.
Enable Protocol Type
Default: No
Selection: Yes or No
Not required. Leave at default value.
Fire Trouble Resound
Default: 0
Selection: 0, 1, 2
0
Keypads do not re-sound the fire
trouble tone.
1
Keypads re-sound the fire trouble
tone at 12:00 PM if any Fire point
that falls within the scope of a keypad
is in an off-normal condition.
2
Keypads re-sound the fire trouble
tone at 12:00 AM if any Fire point
that falls within the scope of a keypad
is in an off-normal condition.
This item determines if a fire trouble condition,
previously acknowledged and silenced at a keypad,
automatically (locally) re-sounds the fire trouble tone at
12:00 PM, 12:00 AM, or not at all if the point is still in
an off-normal state. Events are not generated at the
time the re-sound occurs.