D7212GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 84
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
4.2 Point Responses
4.2.1 Applications for Point Responses 9,
D, and E:
Combine Point Responses 9, D, and E with Perimeter
point types to create more flexible 24-hour protection.
Unlike 24-hour points, a faulted Perimeter point with a
Point Response of D and E displays at the keypad
when arming. Like a 24-hour point, a point
programmed this way can generate alarms whether the
area is armed or disarmed.
Combining Point Response 9 with the Local While
Disarmed feature provides off-site reporting when the
area is armed, but only local alarm annunciation when
the area is disarmed.
Combining Point Response 9 with the Local While
Armed feature provides off-site reporting when the
area is disarmed, but only local alarm annunciation
when the area is armed.
Point Response E: Use this setting for Zonex or ASIC
motion detectors. The control panel can report
troubles while Master Armed.
Point Response F: Does not sound at local keypads
but activates
P## RlyResp Type 1
and keypad faults.
To annunciate the off-normal state at a keypad,
program
Disp as Dvc
as Yes and optionally set
BuzzOn Fault
as 1 or 2. This point response does not
generate alarms or activate an alarm relay.
Point Response 8, 9, A, B, and C: These point
responses provide supervisory (24-hour) reporting.
4.2.2 Characteristics of a Fire Point:
Reporting: When a group of events occurs, the
control panel routes and prints out Fire Reports first.
Visual Annunciation: FIRE TROUBLES continues to
scroll until the trouble clears. When acknowledged, a
FIRE TROUBLE scroll notifies the end user that a Fire
point, or group of Fire points, is still in trouble. Panel-
Wide Relays,
Summary Fire
, and
Summary Fire Tbl
activate if a relay is assigned when any Fire point
enters into alarm or is in trouble.
Audible Annunciation: A Fire point activates the
A# Fire Bell
relay programmed in Relay Parameters.
The amount of time and the pattern of the relay
activation is programmed by area in
Bell Parameters
,
A# Fire Time
, and
A# Fire Pat
.
Supervisory: A Fire point can send a Fire Supervisory
Report and activate the
Summary Fire
Sup
and
Summary Fire Tbl
, Panel-Wide Relays with a
P## Response
of 8-9-A-B-C.
Alarm Verification: A Fire point can delay an alarm
by the length of time programmed in
A# Verify Time
in the Area Parameters. Combined with
A#
Resettable
, a Fire point also resets the electrical circuit
for the amount of time programmed.
Reset Sensor: A fire device that requires resetting can
be manually reset using the reset sensor relay for the
area to which it is assigned.
Fire Walk: Use the Fire Walk function to test Fire
points in the system. The Fire Walk Test automatically
resets each point for five sec when the point is
activated, and rings the Fire Bell for two sec.
To provide an audible tone for a restored
Fire Supervisory point, use P## RlyResp
Type 1 and connect the corresponding
relay to a visual annunciator.