K2200 Series | Installation Guide | 4.0 Six-Wire Bus EN | 20
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
Figure 8: Six-Wire Bus Wiring
Master Controller Slave Controller
+V
AB1
AB2
USD
DSD
-V
Up to 6 Further Slave Controllers
+V AB1 AB2 DSD USD -V
Red
Yellow
White
Green
Blue
Black
+V AB1 AB2 DSD USD -V
+V
AB1
AB2
USD
DSD
-V
Network Controller
+V AB1 AB2 DSD USD -V
SIX WIRE BUS
1 2 3 4 5
6 7 8 9
Red
Yellow
White
Green
Blue
Black
Up to 31 Further Slave Controllers
Slave Controller
4.2 Addresses
The six-wire bus works by each door controller
having its own unique address. The order in which
door controllers are addressed does not matter nor
do they have to be numbered consecutively.
Depending on the type of administration, the
following are possible:
Faceplate Administration - One master controller
(system type 0) and up to 3 slave controllers,
addressed 2,3 and 4.
Readykey for Windows 16 Door - One master
controller (system type 2) addressed 1 and up to
3 slave controllers (system type 3), addressed 2, 3
and 4.
Readykey for Windows 32 Door - One master
controller (system type 2) and up to 7 slave
controllers (system type 3), addressed 2,3,4,5,6,7
and 8.
Network Controller - Single-site - Up to 32 slave
controllers, addressed 1 to 32.
Network Controller - Multi-site
- Via the six wire bus: - Up to 32 slave
controllers (system type 3), addressed 1
to 32.
- Via the serial link:
Up to 32 sites comprising one master
controller (system type 2) address 1 and
up to 7 slave controllers (system type 3),
addressed 2,3,4,5,6,7 and 8.
Up to 95 sites comprising one slave
controller (system type 3).
Note 1:
When being addressed by the CNC, a maximum of 32
controllers can be addressed. When polling, the CNC
display shows the address as 0-9 and A-W (10 to 32).
Note 2:
A multi-site network has sites numbered according to
the type of site as follows:
Site 1 - via six wire bus, one master and up to 32
slaves.
Sites 2-33 - via RS-232, one master and up to seven
slaves.
Sites 34-128 - via RS-232, one master controller only.
Site numbers allocated are dependent on the type of
site and are not necessarily sequential, e.g. a network
could comprise sites 1, 2, 3, 34 and 35.