4 © 2009 Bosch Security Systems, Inc.
3.0 Switch Settings
3.1 Switch 1 - Walk Test
Switch 1
Voltage on WT
Terminal
Walk Test
ON 0 ON
ON +12 OFF
OFF 0 OFF
OFF +12 ON
The Remote Self Test automatically occurs when the walk
test changes from a disabled to enabled by a change in the
voltage on the WT terminals.
The Remote Self Test must be connected to 0 or +12 VDC
on UL listed Control Panels.
3.2 Switch 2 - Alarm Memory Polarity
Switch 2
Voltage on S/U
Terminal
Alarm Memory
ON +12 ON (Locked)
ON 0 OFF (Unlocked)
OFF 0 ON (Locked)
OFF +12 OFF (Unlocked)
The Alarm Memory must be connected to 0 or +12 VDC on
UL listed control panels.
3.3 Switch 3 - Short Range/
Long Range
Switch 3 Range Distance
ON Short 25 ft (8 m)
OFF Long 60 ft (18 m)
3.4 Switch 4 - Antimask ON/
Antimask OFF
Switch 4 Antimask
ON ON
OFF OFF
When Antimask is ON, items placed witihin 1 ft (30 cm)
of the detector are detected. The detector closes the
Trouble contact (terminals marked “TR”) 30 sec after
the detector is blocked.
4.0 LED Indicators
Color Indication Function
Blue Steady ON New alarm detected
Yellow Steady ON Microwave detection
Red Steady ON PIR Detection
Blue Flashing
Detector warming up.
(Up to 2 minutes)
Blue
Flashing 1/4
sec ON, 1/4
sec OFF
Alarm Memory
Blue 3 Flashes Antimask Detected
Blue 4 Flashes
Self Test/
Self Test failure
Blue 5 Flashes Low Input Power
A passing Remote Self Test responds with an
alarm signal.