D9412GV2/D7412GV2
D9412GV2/D7412GV2 Release Notes for Version 7.05
© 2007 Bosch Security Systems, Inc. Page 5 F01U003637-02
3.0 New Features
3.1 Version 7.05 – UL 864 and
ANSI/SIA CP-01 Compliance
3.1.1 UL 864 Compliance
Version 7.04 was skipped during
development and was not released.
Support for D1255RB and D1256RB Keypads, and
D1257RB Annunciator
The D9412GV2 and D7412GV2 Control Panels,
version 7.05 and above, support the new D1255RB
and D1256 Keypads and the new D1257RB
Annunciator. These new devices have four LEDs
added to indicate Fire Alarm, Trouble, Supervisory,
and Alarm Silenced. This LED feature is enabled
automatically when a D125xRB device is installed.
Refer to the D9412GV2/D7412GV2 Program Entry
Guide (P/N: F01U003636-01). Previous versions of the
program entry guide do not include information
related to the D125xRB devices.
Idle Text Scroll Lock
To comply with UL864 9
th
Edition requirements for a
Fire Command Center, set the idle text scroll lock
feature to Yes. Select GV2MAINCOMMAND
CENTERCommand Center Assignments
CC# Idle Scroll Lock. The D125xRB keypad idle
text display locks until a user manually acknowledges
an alarm or trouble condition. The unacknowledged
idle text display updates automatically to the highest
priority alarm or trouble type if one occurs. When the
user presses the [NEXT] key, the idle display is
acknowledged and the scroll is unlocked.
Auxiliary Power Supply Monitor
A new point type is added to monitor auxiliary power
supply modules. If
P# Point Type
is programmed
with 11 – Aux AC Supervision and the associated
point goes off-normal, a Point Trouble condition
occurs immediately. Any Trouble events generated
from an Aux AC Supervision point are delayed by the
time programmed in
AC Fail Time
. This feature is
necessary to comply with UL864 9
th
Edition
requirements.
Battery Recharge Circuit Monitor
Control panel firmware now monitors the battery
recharge circuit to ensure that the backup power of the
control panel is available when needed. If the control
panel detects that the on-board battery is not
recharging correctly because of a hardware failure, a
battery trouble condition occurs. This feature is always
on and cannot be disabled.
Reset Switch Trouble Annunciation
A new feature is added to annunciate trouble locally if
the Reset Switch (S1) is closed. The trouble
annunciation is an intermittent beep from the on-
board sounder. The sounder is silenced when the
switch is opened. This feature is always on and cannot
be disabled.
Fire Bypass Trouble Annunciation
The Fire Bypass warning display is modified to
generate a Trouble warning tone that can be silenced
with [COMMAND][[4]. The trouble condition self-
clears when all bypassed fire points within the
keypad’s scope return to service. This feature is always
on and cannot be disabled.
Summary Fire Relay Options
An option is added that changes the duration of the
Panel Wide Summary Fire Relay output. Select
GV2AUXMISCELLANEOUSFire Summary
Sustain:
Yes Summary Fire Relay clears when all Fire Alarms
are cleared from the display.
No Summary Fire Relay clears when the area Fire
Alarms are silenced and all area Fire Points
return to normal.
The default option is No. This option is consistent
with the Summary Fire Relay operation in the
previous versions of the D9412G and D7412G
Control Panels. This feature provides a way to
maintain the fire strobes after the alarm bell outputs
are silenced.