DS7400XiV4-EXP
DS7400XiV4-EXP Release Notes
© 2005 Bosch Security Systems Page 2 4998154793B
2.1.2 Network Communication Routing
Select how the control panel routes Network
Communication Mode attempts.
Address: 3026
Data Digit:
Data Digit 1: ____ (refer to Table 3;
default = 0)
Data Digit 2: Must = 0
Selections: 0 to 3
Table 3: Network Communication Routing
Select Options 0 1 2 3
Use IP Module 1 only
Use IP Module 2 only
Use IP Module 1 as primary and
Module 2 as backup
Use both IP Module 1 and 2
2.1.3 Network Communication Heartbeat Interval
Set the rate at which the DX4020 polls the receiver.
The heartbeat interval requires four data digits. For
example, to program a five-second heartbeat interval,
program Data Digit 1 as 0, Data Digit 2 as 0, Data
Digit 3 as 0, and Data Digit 4 as 5.
Program the heartbeat interval using HEX values.
Table 4 shows the keypad keys you must press to
generate HEX characters A through F. Table 19 on
page 8 shows the HEX-to-decimal conversion values.
Addresses: 3027
Data Digit:
Data Digit 1: ____
Data Digit 2: ____
Data Digit 3: ____
Data Digit 4: ____
Values: 0 (disabled), 5 sec to 65535 sec
Default: 0000 (disabled)
Selections: 0 to 9, *0 to *5 (hexadecimal values
that display as A through F at the keypads). Use
these selections to enter valid heartbeat values,
such as:
0000 = disabled
0005 = 5 sec
000A = 10 sec
FFFF = 65535 sec
Table 4: HEX Character Values
Keys Pressed HEX Character
[*][0] A
[*][1] B
[*][2] C
[*][3] D
[*][4] E
[*][5] F
2.1.4 Network Communication Wait for Ack Time
Set the amount of time that the DX4020 waits for an
acknowledgment from the receiver before polling it
again.
The wait for acknowledgement time requires four data
digits. For example, to program a five-second ack
time, program Data Digit 1 as 0, Data Digit 2 as 0,
Data Digit 3 as 0, and Data Digit 4 as 5.
The ack time is programmed using HEX values. Table
4 shows the keypad keys you must press to generate
HEX characters A through F. Table 19 on page 8 shows
the HEX-to-decimal conversion values.
Addresses: 3029
Data Digit:
Data Digit 1: ____
Data Digit 2: ____
Data Digit 3: ____
Data Digit 4: ____
Values: 0 (disabled), 5 sec to 65535 sec
Default: 0000 (disabled)
Selections: 0 to 9, *0 to *5 (hexadecimal values
that display as A through F at the keypads). Use
these selections to enter valid ack time values,
such as:
0005 = 5 sec
000A = 10 sec
FFFF = 65535 sec
Zobrazit stránku 1
1 2 3 4 5 6 7 8 9 10