
D7212GV2 | Operation and Installation Guide | 6.0 Power Outputs
.
Bosch Security Systems, Inc. | 2/07 | F01U003805-02 25
6.0 Power Outputs
6.1 Circuit Protection
Three self-resetting circuit breakers protect the control
panel from short circuits on the continuous and
programmable power outputs. If the control panel is
programmed for power supervision and a short circuit
occurs on one of the power outputs, the control panel
sends a
BATTERY LOW or BATTERY MISSING for
Bosch Security Systems, Inc. Modem IIIa
2
Communication Format, or
TROUBLE ZN 9 for BFSK.
One self-resetting circuit breaker protects:
•
Terminal 3: Auxiliary Power
•
Terminal 24: Zonex Power.
A short circuit on one terminal disrupts
power to the other terminals.
Another self-resetting circuit breaker protects:
•
Terminal 6: Alarm Power Output
•
Terminal 7: Alternate Alarm Power Output
•
Terminal 8: Switched Auxiliary Power.
A short circuit on one of the terminals
disrupts power to the other two terminals.
The third self-resetting circuit breaker protects
Terminal 32: Power +.
6.2 Total Available Power
The system produces up to 1.4 A of combined power
at 10.2 VDC to 13.9 VDC for all powered devices. The
outputs listed below share the available power. These
outputs are shown as red circles on the faceplate.
Terminal 3 - Auxiliary Power: Use this terminal to
power devices requiring continuous power.
Terminal 6 (Relay A) - Alarm Power Output:
Programmable relay normally open, power on alarm.
Terminal 7 (Relay B) - Alternate Alarm Power
Output: Programmable relay normally open, power on
alarm.
Terminal 8 (Relay C) - Switched Auxiliary Power:
Programmable relay normally closed, switches power
off when the Sensor Reset command is executed.
Terminal 24 - Zonex Power: Use this terminal to
power Zonex modules such as the D8125, D8128D,
and D8129 Modules.
Terminal 32 - Power +: Use this terminal to power
serial device interface (SDI) devices such as keypads,
the D9131A Parallel Printer Interface Module, and the
D9210B Wiegand Control Interface Module.
6.3 Continuous Power Output
Terminals
3, 8, and 32
The continuous current draw for powered devices
connected to Terminals 3, 8, 24, and 32, and the
accessory connector must not exceed 1.4 A. Devices
powered from these outputs must operate over a range
of 10.2 VDC to 13.9 VDC.
Power Restricted for Fire and Combined Fire and
Burglary Systems: Use the Fire System Power
Formula to calculate the current available for fire and
combined fire and burglary systems (refer to Section 6.4
Programmable Power Output Terminals 6, 7, and 8).
6.4 Programmable Power Output
Terminals 6, 7, and 8
6.4.1 Programming
The power outputs at Terminals 6, 7, and 8 are
programmed as Relays A, B, and C. All relays are
programmed in the Relays section.
Relays are assigned a relay type, (Fire Bell, for
example) when they are assigned to an area. Relays
can be assigned to one or more areas.
The Bosch Security Systems, Inc. defaults set Relay A
(Terminal 6) as a Steady Alarm Bell output, Relay B
(Terminal 7) as a Pulsed Fire Bell output, and Relay C
(Terminal 8) as a Verification or Reset output for
smoke detectors. The D7212GV2 Program Entry Guide
(P/N: F01U003804) contains complete instructions for
programming relays. Refer to Sections 6.4.2 Terminals 6
and 7, 6.4.3 Fire System Power Formula, and 6.4.4
Terminal 8 on page 26 for descriptions of the functions
of each terminal.
Refer to the Bell Parameters section of the program to
set the Fire Bell, Alarm Bell output responses for relays.
Four annunciation patterns are available: Steady,
Pulsed, California Standard, and Temporal Code 3.
Voltage Output at Terminals 6, 7, and 8
If Terminals 6, 7, and 8 do not provide the expected
output, check:
•
Programming for Relays A, B, and C in the relays
section of the program.
•
Bell Parameters section of the program to confirm
that the Alarm and Fire Bell responses are
programmed for the expected duration and
pattern.
Komentáře k této Příručce