D7212GV2 | Operation and Installation Guide | 3.0 Overview
12 Bosch Security Systems, Inc. | 2/07 | F01U003805-02
Table 5: Compatible Keypads and Command
Centers
Model Display Application
D1255/
D1255B/
D1255RB
16-character
alphanumeric
Fire/Burglary/Access
D1256/
D1256RB
16-character
alphanumeric
Fire
D1257/
D1257RB
16-character
alphanumeric
Fire
D1260/
D1260B
4-line by 20-
character
Fire/Burglary
D720/
D720B
8 LED Fire/Burglary
3.3.9 Keyswitch
Maintained or momentary closure devices such as
keyswitches allow any of the four available areas to be
armed or disarmed. Point programming determines the
loop responses and which area a keyswitch controls.
3.3.10 Event Memory
The system uses event memory to store events for each
area. A D1255, D1255B, D1255RB, D1260, or D1260B
Keypad assigned to an area allows viewing of the
events for the area. The control panel clears the events
for an area from event memory and starts storing new
events when the area is master armed.
3.3.11 Event Log
The system stores 500 to 1000 events and event
modifiers from all areas in its event log. Event
modifiers add information about an event to the log.
Some events are always followed by a modifier. For
example, the system adds at least two items to the log
each time an area is armed or disarmed, the open (or
close) event and an event modifier showing the
previous arming state.
All events and their modifiers can be stored even if the
control panel does not send a report for them. The log
can be viewed at a keypad, printed locally using the
D9131A Parallel Printer Interface Module and a
parallel printer, or uploaded using Remote
Programming Software (RPS).
For a list of the log events and event modifiers, refer to
the appendix in the user’s guide for the keypad.
3.3.12 Ground Fault Detection
The Earth Ground Terminal on the control panels is
electrically isolated from all other terminals to allow
the D7212GV2 to detect ground fault conditions. A
Ground Fault Detect Enable switch (S4) is located just
under Terminal 10, Earth Ground, on the control
panel. Refer to Section 4.5.2 Ground Fault Detect Enable
on page 15 for information on operating this function.
3.3.13 Ground Fault Detection Added Feature
When Ground Fault Detect is enabled (S4 closed),
Points 1 to 8 can be used for non-powered fire-
initiating devices such as heat detectors, four-wire
smoke detectors, and pull stations. A D125B Powered
Loop Interface or a D129 Dual Class A Interface
Module is not required when connecting the non-
powered fire-initiating devices to Points 1 to 8.
3.3.14 Conettix Functions
The D6600 Conettix System supports data network
communications. Conettix allows the D6600 receiver to
connect to network topologies, specifically Ethernet.
Conettix also allows this receiver to process messages
to and from most networks using TCP/IP protocols.
Connecting to a data network is possible using the
COM4 or COM1 connection from the D6600 receiver
to the D6680 Network Adapter. Alarm control panels
can send reports through telephone lines or Ethernet
and token-ring data networks to the D6600 receiver
and then to the central station automation software or
the network printer through a local area network
(LAN) or wide area network (WAN). The network can
monitor the status of alarm control panels.
3.3.15 Programming
Use the Bosch Security Systems, Inc. D5200
Programmer or the Remote Programming Software
(RPS) to program the D7212GV2 Control Panel.
Refer to the D7212GV2 Program Entry Guide
(P/N: F01U003804) for programming options.
3.3.16 Other Features
The D7212GV2 Control Panel has many
programmable features. Some of the features are listed
below. Complete details on all features are in the
D7212GV2 Program Entry Guide (P/N: F01U003804).
Supervision of AC (primary power), battery
(secondary power), Zonex and SDI buses, central
processing unit (CPU), up to three printers, and
two telephone lines
Automatic System Test Reports
Remote access for programming, diagnostics, and
log uploads using the remote programming
software (RPS)
Fire alarm verification
Programmable alarm output