D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0 Off-Board Points
.
Bosch Security Systems, Inc. | 2/10 | F01U143070-01 51
Figure 22: D8128D OctoPOPIT Sensor Loops
COM IN OUT+12V P1 COM P2 P3 COM P4 P5 COM P6 P7 COM P8
1
2 3
4
5
1 - D8128D OctoPOPIT
2 - To control panel
3 - To additional OctoPOPIT sensor loops
4 - OctoPOPIT sensor loops
5 - 1 k EOL resistor (P/N: P105BL, package of
eight)
9.5 Testing Off-Board Points
Use the Service Walk Test to test off-board points.
Test to ensure that all off-board points operate
properly.
Walk Test and Service Walk Test Do Not Show
Extra Points: If the point assignment switches on a
POPIT or OctoPOPIT are set incorrectly, missing and
extra points can occur. If the same point number is
assigned to two or more POPITs or OctoPOPITs,
none of the points with that number test correctly.
Refer to Section 9.1 Point (Zonex) Bus: D9412GV3
Terminals and D7412GV3 Terminals on page 38.