D9412GV3/D7412GV3 | Operation and Installation Guide | 4.0 Installation
18 Bosch Security Systems, Inc. | 2/10 | F01U143070-01
If the reset pin is placed in the disable position when
all areas are armed, there must be an entry in the
Answer Armed program item. Refer to RPS
Parameters in the D9412GV3/D7412GV3 Program
Entry Guide (P/N: F01U143071).
Locking the pin in the disable position applies power
to the control panel and charges the battery while the
detection devices and keypads are installed.
Figure 4: Reset Pin
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GREEN DATA BUS B
BLACK COMMON
32
31
30
29
1
2
1 - Reset pin locked (closed)
2 - Reset pin normal (open)
4.6 Completing the Installation
If not already complete, make the earth ground
connection to Terminal 10 and lock the reset pin in
the closed position.
4.6.1 Charging the Battery
Connect the battery, then the transformer to allow the
control panel to charge the battery while you complete
the installation. Refer to Section 5.0 Power Supply on
page 23 for instructions.
On-board Buzzer Sounds at Power Up and Reset:
The system performs a series of self-diagnostic tests
of hardware, software, and programming at power up
and at reset. The buzzer on the control panel sounds
during the tests. The self-diagnostics tests complete
in approximately 1 to 3 sec.
If the control panel fails any test, the buzzer continues
sounding and a System Trouble message appears at
the keypads.
Touch Terminal 10 First: If the on-board buzzer
sounds briefly when the control panel is touched, any
static charge you carry discharges to the control
panel.
Avoid electrostatic discharge. Always
touch Terminal 10, the earth ground
connection, before beginning work on the
control panel.
If the control panel receives an electrostatic
discharge, it might generate Watchdog Reset and
Param Fail events.
4.6.2 Installing and Wiring Detection Devices
Install and wire detection devices and keypads at their
locations throughout the premises. Do not connect
the control panel yet.
Section 8.0 On-Board Points on page 33 contains
instructions for wiring the on-board points to detection
devices. Section 11.0 Arming Devices on page 57
contains instructions for wiring the keypads.
Instructions for wiring the off-board point POPIT
sensor loops are found in the instructions packaged
with the POPIT modules.
4.6.3 Installing Modules and Relays
1. Power down the unit by unplugging the
transformer and disconnecting the battery.
Always power down the unit when
installing modules or relays, or when
making wiring connections to the control
panel.
2. Install and wire any modules required for the
installation as described in the module’s
installation instructions.
Instructions for the D8125 POPEX Module,
D8128D OctoPOPIT Module, D8129 OctoRelay
Module, D811 Arm Status Relay Module, and
D928 Dual Phone Line Switcher appear in this
guide.
Refer to Section 9.0 Off-Board Points on page
38 for D8125 and D8128D instructions. Refer to
Section 10.0 Off-Board Relays on page 52 for
D8129 and D811 instructions. Refer to Section
7.11 D928 Dual Phone Line Switcher on page 32
for D928 instructions.
3. If using the power outputs at Terminals 7 or 8,
refer to Section 6.4 Programmable Power Output
Terminals 6, 7, and 8 on page 27 for
instructions.
4.6.4 Connecting the On-board Points and
Keypads
Connect the on-board points and keypad wiring to the
system. Refer to Section 8.0 On-Board Points on
page 33 and Section 11.0 Arming Devices on page 57
for instructions.