Bosch D7212GV2 Uživatelský manuál Strana 3

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 8
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 2
Scheduled Events (Skeds)
The internal clock and calendar start individually
scheduled events (skeds). Skeds perform functions
such as arm or disarm, relay control, or point
bypassing. The D7212GV2 Control Panel offers:
40 scheduled events with up to 16 different functions
available
Eight opening windows and eight closing windows
Eight user windows
Day-of-week, date-of-month, or holiday only schedules
Four holiday schedules of 366 days each (leap year)
Fire Test
When a user activates Fire Test Mode, the control
panel suppresses all reports to the central station. The
command center and annunciator show all testing
data. An automatic sensor reset feature saves time;
you do not need to reset the sensors manually. At the
end of test, the command center shows the number of
untested points.
Programming, Diagnostics and Controls
Users can program on-site with a D5200 Programmer,
or program remotely through RPS. A programmable
system passcode prevents unauthorized remote
programming.
D7212GV2 Control Panels accommodate up to four
separate telephone numbers for primary, alternate,
and backup receivers for automatic test reports.
When resetting alarms or arming or disarming a
system, the user is identified by name and number.
Certifications and approvals
Region Certification
USA UL AMCX: Central Station Alarm Units
(UL1610, UL1635), AMCX7: Central
Station Alarm Units Certified for Canada
(CAN/ULC-S304-M88, UL 1635),
AMTB: Control Panels, SIA False Alarm
Reduction (ANSI/SIA CP-01-2000),
AOTX: Local Alarm Units (UL464,
UL609), AOTX7: Local Alarm Units Cer-
tified for Canada (CAN/ULC-S303, CAN/
ULC-S525), APAW: Police Station Alarm
Units (UL365, UL464), APAW7: Police
Station Alarm Units Certified for Canada
(CAN/ULC -S303, CAN/ULC-S304,
CAN/ULC-S525), APOU: Proprietary
Alarm Units (UL1076), APOU7: Propri-
etary Alarm Units Certified for Canada
(ULC/ORD-C1076), NBSX: Household
Burglar Alarm System Units (UL1023),
NBSX7: Household Burglar Alarm Sys-
tem Units Certified for Canada (ULC/
ORD-C1023), UTOU: Control Units and
Accessories - Household System Type
(UL985), UTOU7: Control Units and Ac-
cessories - Household System Type Cer-
tified for Canada (ULC-S545)
CSFM 7167-1615:0100 CONTROL UNIT
(HOUSEHOLD)
FCC AJ9-MUL-46532-AL-E
Canada IC 1249A-GV2
Installation/configuration notes
Compatible Products
Keypads D1260 Series Keypads
(D1260, D1260W, D1260R, D1260BLK,
D1260B)
D720 Series Keypads
(D720, D720W, D720R, D720B)
D1255 Series Keypads
(D1255, D1255W, D1255R, D1255B)
D1256 and D1256RB Fire Keypads
D1257 and D1257RB Remote Fire Alarm
Annunciator
D279A Independent Zone Control
Detectors D278S Four-wire Addressable Detector Base
D285/TH Photoelectric Smoke Detector Heads
D298S Addressable Detector Base
D7050 Series Addressable Photoelectric Smoke
and Smoke Heat Detector Heads
F220-B6PM/S Addressable Detector Bases with
POPITs
MX250 Series Smoke Detectors
MX775i Addressable PIR Detector
MX794i Long Range Multiplex PIR Detector
MX934i Addressable PIR Detector
MX938i Addressable PIR Detector
ZX776Z PIR Detector
ZX794Z Long Range PIR Detector
ZX835 TriTech Microwave/PIR Detector
ZX935Z PIR Detector
ZX938Z PIR Detector
ZX970 PIR/Microwave Detector
Bosch conventional detectors, including Blue
Line, seismic, PIR, TriTech PIR Microwave,
photoelectric, heat, and smoke.
Enclosures D8103 Universal Enclosure
D8108A Attack-Resistant Enclosure
D8109 Fire Enclosure
Magnetic Contacts Bosch magnetic contacts include recessed,
terminal connection, miniature, overhead door,
and surface mount.
Modules C900V2 Dialer Capture Module
D113 Battery Lead Supervision Module
D125B Dual Class B Initiating Module
3 | D7212GV2 Control Panel
Zobrazit stránku 2
1 2 3 4 5 6 7 8

Komentáře k této Příručce

Žádné komentáře