GV4 Series | Approved Applications Compliance Guide | 2.0 Optional Compatible Equipment
Bosch Security Systems, Inc. | 3/12 | F01U266055-01 7
Figure 2: Wiring the Rothenbuhler 5110/4001-42 High Security Bell to the GV4 Series Control Panel
1
2
3
4
RED ORG WHT BL K
N/O 1
COMM 1
N/C 1
X1 -
X1+
7
9
123 6
1
2
3
4
5
6
7
10
11
13
8
9
12
6
3
9
9
1 - 5110 Logic Board
2 - 4001-42 External Line Balancing Module
3 - GV4 Series Control Panel
4 - Alarm output
5 - Alternate alarm
6 - Common
7 - +12 VDC
8 - Alarm zone input*
9 - 10 k
resistor
10 - Optional Silence switch
11 - D133 Relay Module
12 - BBL In 4
13 - BBL Out 5
14 - Terminal TB1
*
Use Terminal 11, 13, 14, 17, 19, 20, or 22. (Select only one.)
2.3 Fire Applications
UL Listed fire initiating devices not requiring
electrical compatibility evaluation can be used
in any application. For example, the four-wire
smoke detectors, heat detectors, waterflow
switches, and manual pull stations are suitable
fire initiating devices. Consult the individual
component specification and installation
documents to determine suitability.
The D7212GV4 is not UL Listed for
Commercial Fire.